Maximum Per Channel
5 A @ 120–240 VAC 50/60 Hz, 600 W @ 120 VAC, 1150 W @ 230 VAC, 1200 W @ 240 VAC (0.5 HP), 16 A resistive
Module Total
20 A @ 120–240 VAC 50/60 Hz, 2400 W @ 120 VAC, 4600 W @ 230 VAC, 4800 W @ 240 VAC
Dim Load Types
0–10 V fluorescent ballast or LED driver (4-wire), up to 30 dimmable ballasts/drivers
Switch Load Types
Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent, motors
OUTPUT 1–4 (Dimming Control)
(2) 4-pin 3.5 mm detachable terminal blocks, (4) isolated outputs, 0–10 VDC range, 60 mA max sink per channel, 1024 levels (10-bit)
1–4 (Relay Outputs)
(4) sets of (2) captive screw terminals, isolated Class 1 SPST relays, 5 A max per channel, max wire 12 AWG (2.5 mm²)
NET
(2) 4-pin 3.5 mm detachable terminal blocks, paralleled, Cresnet® slave port
OVERRIDE
(2) 2-pin 3.5 mm detachable terminal blocks, paralleled, low-voltage contact closure input, activates override mode, minimum 10 mA @ 24 V
Channel Controls
(4) red LEDs and (4) miniature pushbuttons for channel status and local control
NET ID
(2) 7-segment green LED digits with (2) pushbuttons for Cresnet ID; digits also display output levels
SETUP
(1) red LED and (1) recessed pushbutton for setup mode and touch-settable ID
OVR
(1) red LED and (1) pushbutton for override mode and saving presets
PWR
(1) green LED indicates DC power on NET port
NET Status
(1) yellow LED indicates communication with control processor
RESET
(1) recessed pushbutton to reset internal processor
Housing
Light gray polycarbonate with label overlay, UL94 V-0 rated
Mounting
35 mm DIN EN 60715 rail mount, DIN 43880 form factor
DIN Space
Occupies 9 DIN modules (162 mm)
Cresnet Power Usage
4.2 W (0.18 A) @ 24 VDC
Operating Temperature
32° to 104°F (0° to 40°C)
Operating Humidity
10% to 90% RH, non-condensing
Heat Dissipation
17 BTU/hr
Dimensions (H×W×D)
3.71 in × 6.26 in × 2.35 in (95 × 159 × 60 mm)
Standards & Certifications